Control Valve Actuator Bench-set and Valve Stroking - Hallo sahabat APLIKASI ELECTRONIC, Pada Artikel yang anda baca kali ini dengan judul Control Valve Actuator Bench-set and Valve Stroking, kami telah mempersiapkan artikel ini dengan baik untuk anda baca dan ambil informasi didalamnya. mudah-mudahan isi postingan Artikel Control Valves, yang kami tulis ini dapat anda pahami. baiklah, selamat membaca.
Judul : Control Valve Actuator Bench-set and Valve Stroking
link : Control Valve Actuator Bench-set and Valve Stroking
Control Valve Actuator Bench-set and Valve Stroking
Actuator Bench-set
Read more »
An actuator bench-set is the instrument air pressure required to begin moving the stem against its closure spring and to fully stroke the actuator over its entire range. These settings are applied by adjusting the spring compression to compensate for the process pressures that will act on the plug area. This setting is typically performed on the actuator before it is mounted onto the valve. The graph below shows the bench-set response of an actuator.
![]() |
Actuator Bench-set Response Graph |
The diagram above is for a direct acting, ATC – FO (air-to-close, fail open) control valve with a signal of 3psig signifying a fully open valve and 15psig a fully closed valve.
Valve Stroking
All control valves after being in service for some time requires stroking. This is because, the valve is a mechanical device with physical components that should be