Instrument Ranges Used in Process Control System Design - Hallo sahabat APLIKASI ELECTRONIC, Pada Artikel yang anda baca kali ini dengan judul Instrument Ranges Used in Process Control System Design, kami telah mempersiapkan artikel ini dengan baik untuk anda baca dan ambil informasi didalamnya. mudah-mudahan isi postingan Artikel Process Control, yang kami tulis ini dapat anda pahami. baiklah, selamat membaca.
Judul : Instrument Ranges Used in Process Control System Design
link : Instrument Ranges Used in Process Control System Design
Instrument Ranges Used in Process Control System Design
In process control design process variables such as temperature, pressure, flow, level, valve signals, analyzers etc are ranged in such a manner to be proportional to the primary signal as much as possible for control purposes. The table below shows the typical instrument scales employed in process control system design:
Instrument Variable | Scale |
Temperature | Direct Reading |
Pressure | Direct Reading |
Flow (differential) | 0 – 100 linear |
Flow (Linearized) | 0 – 100 linear |
Level | 0 – 100 linear |
Analyzer | Direct Reading |
Signal to Valves | 0 – 100% |
As far as possible, the instrument ranges will be selected such that the normal value will be between 50 and 75% of the adjusted range taking into account the specified minimum and maximum values and trip settings will lie between 10% and 90% of the adjusted range.
Typical accuracy of the pressure and differential pressure Smart transmitters will be +/- 0.25% of the calibrated span.
Typical accuracy of temperature Smart transmitters will be +/- 0.3% of the calibrated span.
Typical accuracy of the other transmitters will be as far as possible better than +/- 0.5%.